General | |||
Casing Width (mm) | 17,5 | ||
Connections | Screw terminal | ||
Isolation | 3 way - 1,5 kV RMS | ||
Measurement Error | < 0.2% (Full Scale) | ||
Temperature Coefficient | ≤ 0.004%/°C | ||
Response Time | < 150ms | ||
Sensor Failure Indication | The situation of input signal is at least 10 % different than adjusted value | ||
Protection Class | IP20 | ||
Mounting Type | Rail Mounted | ||
Packing Unit | 1 | ||
Dimensional Drawings | --- | ||
Weight (g) | 42 | ||
Input | Input Type | V , mV , mA | |
Input signal | 0..60mV 0..100mV 0..250mV 0..500mV 0..1V 0..2V 0..2,5V 0..5V 0..10V 0..20V -6..60mV -100..100mV -250..250mV -500..500mV -1..1V -2..2V -2,5..2,5V -5..5V -10..10V -20..20V 0..5mA 0..10mA 0..20mA -5..5mA -10..10mA -20..20mA 4..20mA 0..24mA 4..24mA 0..12mA |
||
Output | Output Signal | 0-5V(0 - 20mA), 5 - 0V(20 - 0mA ), 0 - 10V( 4 - 20mA ), 10 - 0V( 20 - 4mA), -5...5V(20...20mA) | |
Linear Output Range | --- | ||
Max. Load | ≤ 600 Ω ( Current İnput ), ≥ 10K Ω ( Voltage Output ) | ||
Ripple | --- | ||
Supply | Voltage | AC | --- |
DC | 11-30V | ||
Ambient Conditions | Operating Temperature | --- | |
Storing Temperature | -40°C +75°C | ||
Relative Humidity (No Condensation) | Maks. 95% | ||
EMC-EMI | Radiated Emissions Test, 61000-6-2/AC:2012, 61000-6-4:2007/A1:2011 | Any |
602300 | Signal Transducer |